Fire Detection & Fire Alarm System — Design Certificate
Issued in accordance with BS 5839-1:2025, Clause 39.1a & Annex G (Figure G.1)
Project / Job No.:
Document Ref.:
Rev:
G.1 Design certificate — Figure G.1 Model design certificateBS 5839-1:2025
Certificate of design for the fire detection and fire alarm system at:
Address:
I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the design of the fire detection and fire alarm system, particulars of which are set out below, CERTIFY that the said design for which I/we have been responsible complies to the best of my/our knowledge and belief with the recommendations of BS 5839-1:2025, Section 2 for the system category(ies) described below, except for the variations, if any, stated in this certificate.
Name (in block letters):Position:
Signature:
Date:
For and on behalf of:
Address:
Postcode:
The extent of liability of the signatory is limited to the system described below.
System category(ies) (see BS 5839-1:2025, Clause 4):
Quick Select:
Variations from the recommendations of BS 5839-1:2025, Section 2 (see BS 5839-1:2025, Clause 6):
Extent of system covered by this certificate:
Brief description of areas protected (not applicable for Category M, L1 or P1 systems):
Fire Detection & Fire Alarm System — Design Certificate (Continued)
BS 5839-1:2025, Annex G (Figure G.1)
Figure G.1 — Model design certificate (continued)BS 5839-1:2025
Measures incorporated to limit false alarms. Account has been taken of the guidance contained in BS 5839-1:2025, Section 3, and, more specifically (tick as appropriate):
The system includes manual call points. Type and siting of manual call points takes account of the guidance contained in BS 5839-1:2025, Section 3.
The system incorporates automatic detection, and account has been taken of reasonably foreseeable causes of unwanted alarms, particularly in the selection and siting of detectors.
An appropriate analogue addressable system has been specified.
An appropriate multi-sensor system has been specified.
A time-related system has been specified. Details:
Fire alarm signals from automatic fire detectors result initially in a staff alarm, which delays a
general alarm/transmission of signals to an alarm receiving centre
(delete as applicable) for min.
(Click phrase to strike out)
Appropriate guidance has been provided for the user to enable limitation of false alarms.
Other measures as follows:
Installation and commissioning
It is strongly recommended that installation and commissioning be undertaken in accordance with the recommendations of BS 5839-1:2025, Section 4 and Section 5 respectively.
Soak test
In accordance with the recommendations of BS 5839-1:2025, 33.5, it is recommended that, following commissioning, a soak period of
should follow.
(Enter a period of not less than one week.)
As the system incorporates no more than 50 automatic fire detectors, no soak test is necessary to satisfy the recommendations of BS 5839-1:2025.
Verification
Verification that the system complies with BS 5839-1:2025 should be carried out, on completion, in accordance with BS 5839-1:2025, Clause 41:
Maintenance
It is strongly recommended that, after completion, the system is maintained in accordance with BS 5839-1:2025, Section 6.
User responsibilities
The user should appoint a relevant member of the premises management to supervise all matters pertaining to the fire detection and fire alarm system in accordance with the recommendations of BS 5839-1:2025, Section 8.